Weil-McLain · Boiler troubleshooting

Low flame signal

SVF 500/600 Series 1

What is going on

Steps to take when the flame signal stays low.

Likely causes

  • Fouled igniter
  • Poor combustion values
  • Flame sense wiring or ground problem
  • Dirty or restricted heat exchanger
  • Problem in the vent or air piping

Check in this order

  1. Keep the flame sense wire at least 3 inches from the ignition cable, as the ignition cable can cause a false flame reading.
  2. Remove and inspect the igniter with flame sense (see page 109). Clean it if required.
  3. Check the combustion values.
  4. If cleaning does not raise a low flame sense, and the flame sense wiring and ground continuity are good, replace the igniter.
  5. If flame sense stays low after igniter replacement, inspect the vent and air piping.
  6. Inspect and clean the heat exchanger (see pages 111-113).

Applies to: SVF 500/600 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 115. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.