Viessmann · Boiler troubleshooting
Connecting an external heat demand contact
What is going on
Potential-free contact for external heat demand. Use socket X5 for stages 1 and 2 (two-stage burners only) or socket X6 for minimum boiler water temperature.
Check in this order
- Connect the potential-free contact as shown on page 2.
- For stages 1 and 2, plug into socket X5. Burner runs at full output, limited by the adjustable high limit.
- For minimum boiler water temperature, plug into socket X6 and set coding address 32.
- Set coding address 33 for priority control if required.
- Two-stage or modulating burners use load-dependent activation with the minimum temperature option.
Applies to: Switching Module-V with two-stage or modulating burners
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Switching Module-V installation instructions, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.