Connecting an external heat demand contact

Switching Module-V

What is going on

Potential-free contact for external heat demand. Use socket X5 for stages 1 and 2 (two-stage burners only) or socket X6 for minimum boiler water temperature.

Check in this order

  1. Connect the potential-free contact as shown on page 2.
  2. For stages 1 and 2, plug into socket X5. Burner runs at full output, limited by the adjustable high limit.
  3. For minimum boiler water temperature, plug into socket X6 and set coding address 32.
  4. Set coding address 33 for priority control if required.
  5. Two-stage or modulating burners use load-dependent activation with the minimum temperature option.

Applies to: Switching Module-V with two-stage or modulating burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Switching Module-V installation instructions, p. 4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.