Navien · Boiler troubleshooting
Check common vent collar damper through maintenance port
What is going on
Periodic check of the damper plate inside the Navien common vent collar kit to confirm it opens and closes properly.
Check in this order
- Remove the fix screw that holds the maintenance port cover to the common vent collar kit.
- Remove the gasket and the maintenance port cover.
- Look through the maintenance port at the damper plate. It should show OPEN when the boiler is firing and CLOSED when it is off.
- If the damper does not open or close properly, replace the common vent collar kit.
- If condensate comes out of the port, check drainage and look for blockage.
- Reinstall the gasket and the maintenance port cover, then secure with the set screw.
- Visually confirm the gasket sits correctly between the port and the cover.
- Warning the gasket must be properly installed under the cover. Exhaust gas can leak if it is missing or seated wrong, causing carbon monoxide hazard.
Applies to: NCB700 with Navien common vent collar kit (back-draft damper)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 106. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.