Navien · Boiler troubleshooting
Common vent installation requirements
What is going on
Core rules for a shared vent system. Backflow dampers and the cascade cable are required, and the common vent is only approved for altitudes up to 4,500 ft.
Check in this order
- Install a communication cable between all units in the common vent system.
- Install a backflow damper in the exhaust duct of each boiler unit. Use only the damper specified in the manual.
- Use approved PVC cement for pipe joints and elbows.
- Place the boiler units as close as possible to the vent termination.
- Use a new vent system. If an old one is reused, inspect it for punctures, cracks or blockages first.
- Support horizontal vent runs every 4 ft (1.2 m) minimum and vertical runs every 6 ft (1.8 m) minimum.
- Keep the vent termination at least 12 in (305 mm) above ground and above the highest expected snow level, or as local code requires.
- Keep at least 1 ft (30 cm) between the exhaust outlet and expected snow level, and remove snow if needed.
- Do not terminate the vent over public walkways, near soffit or crawl space vents, or where condensate or vapor could cause damage or nuisance.
Applies to: NCB700 common vent installations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 Installation & Operation Manual, pp. 90-91. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.