Common vent installation requirements

NCB700

What is going on

Core rules for a shared vent system. Backflow dampers and the cascade cable are required, and the common vent is only approved for altitudes up to 4,500 ft.

Check in this order

  1. Install a communication cable between all units in the common vent system.
  2. Install a backflow damper in the exhaust duct of each boiler unit. Use only the damper specified in the manual.
  3. Use approved PVC cement for pipe joints and elbows.
  4. Place the boiler units as close as possible to the vent termination.
  5. Use a new vent system. If an old one is reused, inspect it for punctures, cracks or blockages first.
  6. Support horizontal vent runs every 4 ft (1.2 m) minimum and vertical runs every 6 ft (1.8 m) minimum.
  7. Keep the vent termination at least 12 in (305 mm) above ground and above the highest expected snow level, or as local code requires.
  8. Keep at least 1 ft (30 cm) between the exhaust outlet and expected snow level, and remove snow if needed.
  9. Do not terminate the vent over public walkways, near soffit or crawl space vents, or where condensate or vapor could cause damage or nuisance.

Applies to: NCB700 common vent installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 Installation & Operation Manual, pp. 90-91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.