Viessmann · Boiler troubleshooting
Service (maintenance) display
What is going on
The Service message and symbol appear once the hours-run or time limits set in coding 21 and 23 in the Boiler group are reached. The limit values are not listed on these pages. If service is done early, coding 24:1 stays set and must be changed to 24:0, or Service will show again the following Monday.
Likely causes
- Hours-run or time limit from coding 21 or 23 has been reached
Check in this order
- Tap Confirm when the Service message appears.
- If several faults are showing, tap Service messages to view the list.
- Carry out the maintenance.
- If service was done early, set coding 24:1 in the Boiler group to 24:0.
- Or from the home screen Menu, Service, enter viservice, Service functions, Reset service.
Applies to: Vitotronic 300 GW6B boiler control unit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.