Fixed high limit test #2 (valve closed, flow switch jumpered)
What is going on
Alternate high limit test. The boiler is run at high fire with the boiler valve closed. Jumpering the flow switch may be needed for testing. Only do this where required by law.
Check in this order
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. The boiler should shut down by the coding card (on B2TB models, set coding address 06 to maximum) but keep heating until the fixed high limit trips.
- After the fixed high limit trips, slowly open the boiler valve to cool the boiler down safely.
Applies to: Models 112, 150, 399, 530
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.