Clean the heat exchanger - flue side
What is going on
Remove the cleanout plate and burner, then clean the flueways.
Check in this order
- Follow the shutdown steps close the external manual gas valve, disconnect power, and let the boiler cool.
- Do not drain the boiler unless it will be exposed to freezing; do not drain if freeze prevention fluid is used.
- Remove the cleanout plate nuts with a 13 mm wrench or socket.
- Remove the cleanout plate carefully to protect its gasket.
- Remove the burner, piping end combustion chamber access plate, and blower/venturi/mixing tube assembly (see page 91).
- Use the heat exchanger cleaning tool or 20-gauge sheet metal (¾ in wide, about 18 in long) to loosen deposits through the pins at 45° down, 45° up, and horizontal.
- Vacuum debris out of the base through the flue inspection opening.
- Disconnect the condensate line at the bottom of the heat exchanger and place a pan under the trap connection.
- Spray water through combustion chamber openings onto the pins until debris is flushed into the base.
- Spray water into the flue inspection opening and through the condensate line.
- Reinstall the condensate line and flue inspection plug.
- Inspect the cleanout plate gasket and replace it if damaged.
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 102-103. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.