Viessmann · Boiler troubleshooting

Conversion to natural gas (NG)

Vitocrossal 200 CM2

What is going on

Convert the burner from LPG back to natural gas. No separate orifice is needed for natural gas.

Check in this order

  1. Close the gas shut-off valve.
  2. Switch off the system ON/OFF switch at the boiler control unit.
  3. Switch off the main boiler circuit breaker or power supply and prevent reconnection.
  4. Remove the boiler front cover.
  5. Undo gas supply fitting A and disconnect compensation tubing B.
  6. Remove four 8 mm hex nuts and detach the gas valve from flange C.
  7. Remove and dispose of the LPG orifice D and the rubberized cork gaskets E.
  8. Install a new rubberized cork gasket between the gas valve and flange C.
  9. Secure the gas valve to flange C. Torque nuts diagonally to 17.7 lb-in (2.0 Nm).
  10. Secure and tighten gas supply fitting A and reconnect compensation tubing B.
  11. Apply the partial rating plate, the labels and complete the conversion report.
  12. Check all gas fittings for leaks.

Applies to: Vitocrossal 200 CM2 186 to 311 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.