Conversion to natural gas (NG)
What is going on
Convert the burner from LPG back to natural gas. No separate orifice is needed for natural gas.
Check in this order
- Close the gas shut-off valve.
- Switch off the system ON/OFF switch at the boiler control unit.
- Switch off the main boiler circuit breaker or power supply and prevent reconnection.
- Remove the boiler front cover.
- Undo gas supply fitting A and disconnect compensation tubing B.
- Remove four 8 mm hex nuts and detach the gas valve from flange C.
- Remove and dispose of the LPG orifice D and the rubberized cork gaskets E.
- Install a new rubberized cork gasket between the gas valve and flange C.
- Secure the gas valve to flange C. Torque nuts diagonally to 17.7 lb-in (2.0 Nm).
- Secure and tighten gas supply fitting A and reconnect compensation tubing B.
- Apply the partial rating plate, the labels and complete the conversion report.
- Check all gas fittings for leaks.
Applies to: Vitocrossal 200 CM2 186 to 311 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.