Weil-McLain · Boiler troubleshooting

Purge air from the water system

SlimFit Series 2

What is going on

Air is removed zone by zone through the purge valve, then the remaining air vents are opened.

Likely causes

  • Air trapped in zones or at high points

Check in this order

  1. Connect a hose to the purge valve and route it to a drain where flow can be seen.
  2. Close the boiler or system isolation valve between the purge valve and the fill connection.
  3. Close the zone isolation valves.
  4. Open the quick-fill valve on the cold make-up line and open the purge valve.
  5. Open one zone isolation valve at a time and run water until no air flow is seen. Close it and move to the next zone.
  6. Close the quick-fill and purge valves, remove the hose, and open all isolation valves.
  7. Watch the system pressure rise to the correct cold-fill pressure.
  8. If no purge valves are installed, open manual vents one at a time from the lowest floor until water squirts out.
  9. Open the automatic air vent one turn on diaphragm or bladder tank systems.
  10. Refill to the correct pressure.

Applies to: SlimFit Series 2 startup

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual, p. 79. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.