Purge air from the water system
What is going on
Air is removed zone by zone through the purge valve, then the remaining air vents are opened.
Likely causes
- Air trapped in zones or at high points
Check in this order
- Connect a hose to the purge valve and route it to a drain where flow can be seen.
- Close the boiler or system isolation valve between the purge valve and the fill connection.
- Close the zone isolation valves.
- Open the quick-fill valve on the cold make-up line and open the purge valve.
- Open one zone isolation valve at a time and run water until no air flow is seen. Close it and move to the next zone.
- Close the quick-fill and purge valves, remove the hose, and open all isolation valves.
- Watch the system pressure rise to the correct cold-fill pressure.
- If no purge valves are installed, open manual vents one at a time from the lowest floor until water squirts out.
- Open the automatic air vent one turn on diaphragm or bladder tank systems.
- Refill to the correct pressure.
Applies to: SlimFit Series 2 startup
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual, p. 79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.