Pilot lights but main flame does not light

EG / PEG Series 7

What is going on

Pilot is established but the main burners do not light.

Likely causes

  • Main gas valve not energized
  • Manual gas valve closed
  • Manifold pressure incorrect during main ignition

Check in this order

  1. Verify both main gas valves are being energized with 24 Vac.
  2. Verify all manual gas valves are in the open position.
  3. Verify manifold pressure during main flame ignition.

Applies to: EG water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.