Install and check the DHW tank temperature sensor
What is going on
Sensor for single-boiler systems with DHW heating. Do not connect it on systems without DHW heating.
Check in this order
- Install the DHW tank temperature sensor following the DHW tank installation instructions.
- When fitting the sensor in a tank of another make, press it against the tank's sensor well with a suitable device.
- Make sure the maximum permitted DHW temperature cannot be exceeded; fit a suitable safety device if needed.
- Disconnect the sensor from the terminals and measure its resistance at plug terminals 1 and 2.
- Compare the reading with the tank temperature and replace the sensor if the difference is significant.
- Reconnect the plug after the check. On systems without DHW heating, leave the sensor unconnected.
Applies to: Vitotronic 300-K MW1S DHW tank temperature sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.