Rinnai · Boiler troubleshooting
Massachusetts requirements for side wall horizontal gas venting
What is going on
For gas models sold in Massachusetts with a side wall horizontal vent terminal less than 7 ft above finished grade, including over decks and porches. Only a properly trained licensed professional may install this direct-vent unit. Confirm these items are in place before the inspector signs off.
Check in this order
- Confirm a hard-wired CO detector with alarm and battery back-up is installed on the floor level where the boiler is installed.
- Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level served by the vent.
- If the boiler is in a crawl space or attic, the hard-wired detector with battery back-up may go on the next adjacent floor level.
- If the requirements cannot be met at completion, the owner has 30 days to comply. A battery-operated CO detector with alarm must be installed during that period.
- Use CO detectors that meet NFPA 720, are ANSI/UL 2034 listed and are IAS certified.
- Mount a metal or plastic sign on the building exterior at least 8 ft above grade, directly in line with the vent terminal. Lettering must be at least 1/2 inch high and read: "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS."
- Expect the state or local gas inspector to withhold approval unless the CO detectors and signage meet 248 CMR 5.08(2)(a)1 through 4.
Applies to: Gas models sold in Massachusetts, side wall horizontal vent under 7 ft above grade
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation manual, p. 145. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.