Weil-McLain · Boiler troubleshooting

Sensor wiring and supply/return sensor failure

SVF Series 1

What is going on

The control compares return temperature to supply temperature. If the return reads higher than the supply, it assumes a sensor problem and reports it on the display. The system will not heat properly without both sensors installed correctly.

Likely causes

  • Supply or return sensor not installed in the correct piping
  • Sensor wiring open, shorted or on the wrong terminals
  • Return reading above supply reading

Check in this order

  1. Install the supply sensor on the system supply piping, at least six pipe diameters and no more than 3 ft from the boiler connection.
  2. Install the return sensor on the system return piping.
  3. Wire the supply sensor between P14 #1 and #2 (common).
  4. Wire the return sensor between P14 #3 and #2 (common).
  5. Thermostat wire may be used for the sensor leads.
  6. If the display reports a sensor problem, check placement and wiring at both sensors.

Applies to: System supply and return sensors

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.