Viessmann · Boiler troubleshooting

Limit maximum heating output

Vitocrossal 200 CI2

What is going on

Set a cap on heating output using the modulation range. Make sure the heat transfer and flow rate are adequate before you set the limit. Factory setting is 100%.

Check in this order

  1. Tap the menu button and select Service.
  2. Enter password viservice and confirm.
  3. Select System configuration, then Boiler.
  4. Open parameter 596.0 Maximum heating output.
  5. Check that sufficient flow is ensured; increase heat transfer if needed, then confirm the prompt.
  6. Enter the required value as a percent of rated heating output and confirm.
  7. End service functions.

Applies to: Vitocrossal 200 CI2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.