Viessmann · Boiler troubleshooting
Limit maximum heating output
What is going on
Set a cap on heating output using the modulation range. Make sure the heat transfer and flow rate are adequate before you set the limit. Factory setting is 100%.
Check in this order
- Tap the menu button and select Service.
- Enter password viservice and confirm.
- Select System configuration, then Boiler.
- Open parameter 596.0 Maximum heating output.
- Check that sufficient flow is ensured; increase heat transfer if needed, then confirm the prompt.
- Enter the required value as a percent of rated heating output and confirm.
- End service functions.
Applies to: Vitocrossal 200 CI2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.