Weil-McLain · Boiler troubleshooting
Operate the boiler relief valve (every 6 months)
What is going on
Manually lift the relief valve lever to confirm it passes water and reseats.
Likely causes
- Valve or discharge line blocked
- Valve weeping after lifting
Check in this order
- Confirm the discharge pipe runs to a safe drain point and cannot scald anyone.
- Read the boiler gauge to confirm the system is pressurized.
- Lift the relief valve lever slightly so water flows through the valve and discharge pipe.
- If water flows freely, release the lever and let the valve seat.
- Watch the discharge pipe to confirm the valve does not weep after it has drained.
- If the valve weeps, lift it again to try to clean the seat; if it still weeps, call a technician.
- If no water flows when the lever is fully lifted, shut the boiler down per the jacket instructions and call a technician.
Applies to: All boilers in this manual
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.