Operate the boiler relief valve (every 6 months)

CGa Series 4CGi Series 5EG Series 7PEG Series 7LGB Series 2 & 3

What is going on

Manually lift the relief valve lever to confirm it passes water and reseats.

Likely causes

  • Valve or discharge line blocked
  • Valve weeping after lifting

Check in this order

  1. Confirm the discharge pipe runs to a safe drain point and cannot scald anyone.
  2. Read the boiler gauge to confirm the system is pressurized.
  3. Lift the relief valve lever slightly so water flows through the valve and discharge pipe.
  4. If water flows freely, release the lever and let the valve seat.
  5. Watch the discharge pipe to confirm the valve does not weep after it has drained.
  6. If the valve weeps, lift it again to try to clean the seat; if it still weeps, call a technician.
  7. If no water flows when the lever is fully lifted, shut the boiler down per the jacket instructions and call a technician.

Applies to: All boilers in this manual

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.