Weil-McLain · Boiler troubleshooting
Sizing combustion and ventilation air openings
What is going on
Openings are sized in free area after louver losses. A single opening may be used if it starts within 12 in of the ceiling and meets the clearance and direct-to-outdoors rules. Its free area must equal at least the sum of all vent connectors in the space and at least 1 sq in per 3000 Btuh of input. In tight construction, use two openings (one within 12 in of the ceiling, one within 12 in of the floor) at 1 sq in per 1000 Btuh of all appliances. No openings are needed if the space volume is at least 50 cu ft per 1000 Btuh of all installed appliances, and the building is not tight construction.
Likely causes
- Space under negative pressure from exhaust fans or air movers
- Motorized air damper fails to open or closes during firing
Check in this order
- Sum the input of all appliances in MBH and check the opening or volume requirement.
- Size the opening free area for the vent connectors and the input rating.
- If a motorized damper is used, interlock it so the boiler will not fire unless it is fully open.
- Wire an isolated proving contact for the damper in series with the thermostat input so the boiler shuts down if the damper closes.
- Make sure the space is never under negative pressure.
Applies to: Boiler room air supply
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, pp. 13-14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.