Simultaneous DHW and CH Is Not Functional (Combi Only)
What is going on
Boiler does not run DHW and CH at the same time.
Likely causes
- Parameter 08 off
- CH set point below 140°F/60°C (not allowed, including outdoor reset)
- DHW inlet temperature too hot
- DHW and CH heating loads beyond limits together
Check in this order
- Confirm parameter 08 is ON.
- Set the CH set point to 140°F/60°C or higher (outdoor reset settings included).
- Confirm the DHW inlet temperature is not too hot.
- Confirm the DHW and CH loads are within limits for simultaneous operation.
Applies to: I-Series Plus combi boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 117. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.