Rinnai · Boiler troubleshooting

Simultaneous DHW and CH Is Not Functional (Combi Only)

I-Series Plus

What is going on

Boiler does not run DHW and CH at the same time.

Likely causes

  • Parameter 08 off
  • CH set point below 140°F/60°C (not allowed, including outdoor reset)
  • DHW inlet temperature too hot
  • DHW and CH heating loads beyond limits together

Check in this order

  1. Confirm parameter 08 is ON.
  2. Set the CH set point to 140°F/60°C or higher (outdoor reset settings included).
  3. Confirm the DHW inlet temperature is not too hot.
  4. Confirm the DHW and CH loads are within limits for simultaneous operation.

Applies to: I-Series Plus combi boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 117. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.