Antifreeze limits and precautions
What is going on
Antifreeze concentration must not exceed 50% by volume. Higher concentrations can cause sludge and heat exchanger damage.
Check in this order
- Drain and flush the system before adding antifreeze, and flush any glycol system before installing the boiler.
- Install a water meter or monitor make-up water if automatic fill is used.
- Test antifreeze concentration at least annually. If low, add antifreeze or drain and refill.
- Keep the MSDS for the fluid with the owner.
Applies to: SVF 500/600 Series 1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 93. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.