Viessmann · Boiler troubleshooting

Remove front panel and burner

Vitodens 100-W, WB1B

What is going on

Isolate power and gas before service. Do not lay the burner on its cylindrical tube.

Check in this order

  1. Isolate and lock out the main power supply and shut off the main gas supply.
  2. Loosen the bottom screws of the front panel without removing them fully, then remove the panel.
  3. Switch the burner off at the main service switch and shut off the gas supply.
  4. Unplug the cables from the fan motor, gas valve and electrode block.
  5. Pull the Venturi extension from the fan.
  6. Release the gas supply pipe fitting. A gasket sits between the gas valve and this connection.
  7. Remove the four Torx T-30 screws and take the burner out.

Applies to: Vitodens 100-W, WB1B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 67-68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.