Viessmann · Boiler troubleshooting
Replace the flow limiter
What is going on
Water can leak when the flow limiter is replaced. Shut off the cold water supply and drain the DHW line and the plate type heat exchanger (DHW side) first.
Likely causes
- Faulty flow limiter
Check in this order
- Shut off the cold water supply.
- Drain the DHW line and the plate type heat exchanger (DHW side).
- Drain the boiler and CombiPLUS.
- Remove the screws from the cover and remove the cover.
- Undo screws A.
- Remove the cap B.
- Remove the faulty flow limiter C.
- Select a new flow limiter that matches the boiler size on the rating plate. The size table is on page 26 of the installation instructions, not in this extract.
- Insert the new flow limiter C.
- Fit the new cap B provided.
Applies to: CombiPLUS flow limiter
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.