Viessmann · Boiler troubleshooting
Return temperature protection with shunt pump (Circuit Diagram 5)
What is going on
Sensor T2 switches on the shunt pump when return temperature falls below the minimum. If the minimum is still not reached, reduce supply at least 50% using sensor T1 through the isolation valve or the heating circuit controls.
Likely causes
- Return temperature below required minimum
Check in this order
- Confirm sensor T2 switches the shunt pump on when return temperature is low.
- If minimum return temperature is not reached, set supply reduction of at least 50% via sensor T1.
- Size the shunt pump so bypassed water is about 30% of the total boiler supply rate.
Applies to: Multi-boiler system with manifold close to boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.