Navien · Boiler troubleshooting

Recover a lost gateway password

Modbus/BACnet Gateway

What is going on

Support must issue a temporary password before a new one can be set.

Likely causes

  • Password lost

Check in this order

  1. Click cancel on the password authentication popup.
  2. Email the password recovery token to technical support.
  3. Use the temporary password from support to access the gateway.
  4. Set a new password.

Applies to: Gateway web access

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Modbus/BACnet Gateway Start-up Guide, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.