Viessmann · Boiler troubleshooting

Check running supply pressure (NG or LPG)

Vitocrossal 200 CI2

What is going on

Measure supply pressure with the burner at maximum output. Use a gauge with at least 0.04 in w.c. resolution. Do not open any flame near the boiler.

Check in this order

  1. Start the burner.
  2. Set the burner to maximum heating output using the actuator test at maximum heat input in the service menu. Parameter 596 sets the target but is not applied in the actuator test.
  3. Measure the running supply pressure and compare with the pressure table.
  4. Record the actual value on the maintenance record (page 95).
  5. Close the gas shut-off valve.
  6. Remove the pressure tester and close test nipple A.
  7. Check for leaks with soap and water only. Never use matches, candles or flame, and never purge gas into the combustion chamber.

Applies to: Vitocrossal 200 CI2 399 to 2000 MBH

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.