Viessmann · Boiler troubleshooting
System version 1: direct connection to heating circuit loop
What is going on
Heating circuit is connected directly to the loop from supply and return manifolds. The control runs the heating circuit pump through the power/pump module. Optional high limit aquastat is wired in series with the heating pump. Outdoor sensor, supply sensor and external controls connect to the control unit.
Check in this order
- Wire the power supply (120 VAC, 6FLA) to the power/pump module.
- Wire the heating circuit pump from the power/pump module.
- Connect the outdoor sensor to X3, the supply sensor to X6, and external controls to X5.
- If fitting the optional high limit aquastat, remove the jumper from L-L first.
Applies to: Heating circuit with direct connection to the loop
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H installation and service instructions, p. 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.