Viessmann · Boiler troubleshooting

Check return temperature sensor

Vitotronic 100 GC1

What is going on

Strap-on or immersion sensor for boiler return temperature. Plugs into socket 17A or 17B.

Check in this order

  1. Disconnect the sensor plug (aJA or aJB) in the boiler control terminal compartment.
  2. Measure the resistance between terminals 1 and 2 of the plug.
  3. Compare the reading with the current return temperature using the resistance table.
  4. If the value differs significantly, check the installation and replace the sensor if needed.

Applies to: Boiler return temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 123. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.