Viessmann · Boiler troubleshooting

Mount the Vitotronic 300-K control unit

Vitotronic 300-K

What is going on

The control mounts on a metal backplate, with a mid plate and connection enclosure between the backplate and the control rear section.

Check in this order

  1. Fasten the metal backplate to the mounting surface with four fasteners.
  2. Position the mid plate between the backplate and the connection enclosure.
  3. Install the mid plate and connection enclosure onto the backplate.
  4. Fasten the connection enclosure and mid plate to the backplate with two fasteners.
  5. Install the control rear section onto the connection enclosure housing, hook it onto the backplate tabs, and pivot it downwards.
  6. Fasten the control rear section to the connection enclosure with two fasteners.

Applies to: Vitotronic 300-K

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K installation and service instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.