Viessmann · Boiler troubleshooting

Convert boiler from natural gas to LPG

Vitocrossal 300 CU3A

What is going on

Field conversion of the gas valve and control settings. Use the fuel conversion kit instructions and label.

Check in this order

  1. Set adjusting screw A on the gas valve to "2".
  2. Turn the ON/OFF switch "8" ON.
  3. Enter service functions, call up code 2 (General).
  4. In coding address 11, select value 9.
  5. In coding address 82, select value 1 (LPG operation).
  6. Set coding 11 to any value other than 9.
  7. End service functions.
  8. Open the gas shut-off valve.
  9. Apply the fuel conversion label from the kit as shown in its instructions.

Applies to: Vitocrossal 300 CU3A, natural gas to LPG

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.