Flue CO2 reading outside range
What is going on
Measured CO2 is more than 1% outside the target range for the fuel.
Likely causes
- Leaks in the balanced flue or venting system.
- Gas flow needs adjustment at high or low fire.
Check in this order
- Check the venting system for leaks using the Vitodens venting instructions.
- Check the seals in the balanced flue system.
- Re-measure CO2 at high fire and low fire once steady.
- Adjust high fire with screw B and low fire with the cover C screw as needed.
- Record the actual values in the service report.
Applies to: Vitodens 100-W WB1B combustion check
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 62-63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.