Viessmann · Boiler troubleshooting

Flue CO2 reading outside range

Vitodens 100-W WB1B

What is going on

Measured CO2 is more than 1% outside the target range for the fuel.

Likely causes

  • Leaks in the balanced flue or venting system.
  • Gas flow needs adjustment at high or low fire.

Check in this order

  1. Check the venting system for leaks using the Vitodens venting instructions.
  2. Check the seals in the balanced flue system.
  3. Re-measure CO2 at high fire and low fire once steady.
  4. Adjust high fire with screw B and low fire with the cover C screw as needed.
  5. Record the actual values in the service report.

Applies to: Vitodens 100-W WB1B combustion check

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 62-63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.