Viessmann · Boiler troubleshooting
Adjust the adjustable high limit to 100°C
What is going on
Field change of the adjustable high limit from the factory 95°C to 100°C.
Check in this order
- Disconnect power to the control and the burner.
- Lever out and remove the selector knob R behind the hinged cover, using a suitable screwdriver.
- Break off the marked cams on the stop dial with pointed pliers, as shown in the figure.
- Refit selector knob R so the marking sits in the centre of the selected range.
- Confirm coding address 06 is set as required.
Applies to: Vitotronic 100 GC1 adjustable high limit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.