Viessmann · Boiler troubleshooting

System Layout 7: direct circuit with system separation

Vitodens 200-W B2HB

What is going on

Radiator circuit connected directly to the boiler and an underfloor circuit with system separation, plus DHW. Total flow is less than boiler maximum.

Check in this order

  1. Size the plate heat exchanger secondary pressure drop to be less than or equal to the mixing valve pressure drop.
  2. Install the accessory kit for the mixing valve circuit.
  3. Use a low-loss header if the flow rate exceeds the boiler maximum or is unknown.
  4. Run the DHW circulating pump into the boiler as shown.

Applies to: Direct radiator circuit plus underfloor with plate heat exchanger

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W, B2HB technical data manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.