Chimney and venting general requirements
What is going on
All combustion products must go outdoors through a chimney sized and insulated for this boiler's low flue gas temperatures. Oversized or uninsulated chimneys cause corrosive condensation. The VD2A is not approved for side wall venting.
Likely causes
- Chimney too large or not insulated, so flue gas cools too fast and condenses
- Vent connection not insulated
Check in this order
- Size the chimney for the boiler model and input. If a calculated diameter falls between two sizes, choose the larger one.
- Insulate the chimney connection from the vent pipe collar to the chimney.
- Do not assume the vent collar diameter sets the chimney size.
- Install a barometric draft regulator in the chimney or vent.
- Never run the boiler without an installed venting system.
- Follow local and national codes. Canada: CAN/CSA B149.1 or .2 for gas, CSA B-139 for oil. USA: NFPA 54 venting provisions and ANSI Z223.1 for gas, NFPA 31 for oil.
- Do not stand on the top panel when installing or insulating overhead piping or venting.
Applies to: Vitorond 200 VD2 320 to 1080; VD2A not for side wall venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.