Viessmann · Boiler troubleshooting

Chimney and venting general requirements

Vitorond 200 VD2

What is going on

All combustion products must go outdoors through a chimney sized and insulated for this boiler's low flue gas temperatures. Oversized or uninsulated chimneys cause corrosive condensation. The VD2A is not approved for side wall venting.

Likely causes

  • Chimney too large or not insulated, so flue gas cools too fast and condenses
  • Vent connection not insulated

Check in this order

  1. Size the chimney for the boiler model and input. If a calculated diameter falls between two sizes, choose the larger one.
  2. Insulate the chimney connection from the vent pipe collar to the chimney.
  3. Do not assume the vent collar diameter sets the chimney size.
  4. Install a barometric draft regulator in the chimney or vent.
  5. Never run the boiler without an installed venting system.
  6. Follow local and national codes. Canada: CAN/CSA B149.1 or .2 for gas, CSA B-139 for oil. USA: NFPA 54 venting provisions and ANSI Z223.1 for gas, NFPA 31 for oil.
  7. Do not stand on the top panel when installing or insulating overhead piping or venting.

Applies to: Vitorond 200 VD2 320 to 1080; VD2A not for side wall venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.