Viessmann · Boiler troubleshooting

Clean the burner and gauze assembly

Vitocrossal 200 CI2

What is going on

Cleaning and inspection of the burner. Same procedure for 399/500 and 750/1000 MBH burners, with the 750/1000 unit also having a burner baffle plate.

Check in this order

  1. Remove the electrodes.
  2. Undo the 4 nuts and remove the burner gauze assembly, insulation sections and gaskets.
  3. Replace damaged components and use new gaskets.
  4. Reassemble in reverse order and tighten to the torque table for the burner size.
  5. Make sure the gasket between the fan housing and burner plate is seated correctly.
  6. If no parts are damaged, a visual check is enough; otherwise blow compressed air through the gauze assembly after detaching the fan.
  7. Clean the burner door from the outside with the gauze assembly facing up.
  8. Check for gas tightness after reassembly.

Applies to: Vitocrossal 200 CI2 burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 29-30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.