Viessmann · Boiler troubleshooting
External contacts A, B and C on A2
What is going on
Dry contacts on A2 for heating program change, external disable and external heat demand. Heating circuit allocation uses coding addresses 91, 9A, 99 and 9b.
Check in this order
- Wire the external contacts on A2 per the overview on pages 58 and 59 and the control panel wiring diagram.
- Contact A closing it changes the heating program or opens the mixing valves. Allocate heating circuits with coding addresses 91 and 9A.
- Contact B closing it shuts the burner down or closes the mixing valve. Allocated boiler or shunt pumps switch off and isolation valves close. Allocate with coding address 99.
- Contact B overrides contact A closed mixing valve has priority over open mixing valve.
- Contact C closing it starts the burners as needed to reach the set point at coding address 9b. Supply temperature is limited by the set minimum and maximum supply temperatures.
- Note that heating circuits are not frost protected while the mixing valve is closed, and the minimum boiler return temperature is not maintained during external disabling.
Applies to: Vitotronic 300-K MW1S external dry contacts
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 66. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.