No space heat - Navien NHB-H / NFB-H
What is going on
Thermostat calls for heat but the boiler does not heat the zones and shows no error code.
Likely causes
- Set temperature too low or outdoor reset / WWSD holding heat off
- Boiler off, no power or in standby
- Boiler busy with indirect DHW (DHW priority)
- Thermostat DIP switch or zone settings wrong
- Pump or zone valve not powered
Check in this order
- Check the space heating set temperature; with outdoor reset on, check the outdoor temperature against WWSD (default OFF) and the curve.
- Make sure the boiler has 120 V power and is turned on with the Power button.
- If the indirect tank is calling, space heating waits up to the DHW Priority Time (default 30 min).
- Check DIP SW2 #7: OFF = thermostat used, ON = unused (continuous operation).
- Check Input/Output Status is the thermostat input seen, and are the boiler pump, zone pumps or zone valves energized?
- Run Test Mode for the pumps and zone valves to confirm they operate; check Zone Settings (pump vs valve system) match the install.
- Check Error History for codes that cleared on their own.
- Press Back to reset. If still no heat, call Navien technical support 1-800-519-8794.
Applies to: Navien NHB-H and NFB-H condensing boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NHB-H User's Information Manual (V1.0 Apr 2024), 5.1 Solving Basic Problems p.23; NHB-H Installation and Operation Manual 6.2 p.68, 11.8-11.9 p.104-108, 11.13 p.110-117. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.