Fill and flush heating system

Vitodens 200-W B2HA

What is going on

Use clean potable water and flush the piping before filling. Debris can settle in the boiler and cause overheating damage that is not covered by warranty.

Check in this order

  1. Flush the entire heating system before filling.
  2. Open system isolation valves C and D if installed, after confirming required flow check valves are fitted.
  3. Check the expansion tank precharge against the static pressure. If nitrogen pressure is lower, raise the membrane pressure slightly above system pressure.
  4. Connect a hose from a fresh water supply to the boiler fill tap.
  5. Open the water supply, then slowly open the boiler fill tap with isolation valves closed.
  6. Flush the heat exchanger through supply and return for at least 10 minutes until air is removed.
  7. When the boiler drain runs water, close the boiler drain, then the boiler fill valve, and open the system isolation valves.
  8. Check system pressure.

Applies to: Vitodens 200-W B2HA 19, 28, 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 13-14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.