Navien · Boiler troubleshooting

Update gateway firmware

Modbus/BACnet Gateway

What is going on

Load new firmware through the web browser.

Check in this order

  1. Extract the new file and save it to the local PC.
  2. Open a browser and enter the FieldServer IP address (default 192.168.1.24).
  3. If the IP is unknown, use FS Toolbox.
  4. Click Diagnostics & Debugging, then Setup, then File Transfer, then the General tab.
  5. Click Choose Files and select the web.img file.
  6. Click the orange Submit button.
  7. When the download completes, click System Restart.

Applies to: Gateway firmware

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Modbus/BACnet Gateway Start-up Guide, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.