Navien · Boiler troubleshooting
Update gateway firmware
What is going on
Load new firmware through the web browser.
Check in this order
- Extract the new file and save it to the local PC.
- Open a browser and enter the FieldServer IP address (default 192.168.1.24).
- If the IP is unknown, use FS Toolbox.
- Click Diagnostics & Debugging, then Setup, then File Transfer, then the General tab.
- Click Choose Files and select the web.img file.
- Click the orange Submit button.
- When the download completes, click System Restart.
Applies to: Gateway firmware
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Modbus/BACnet Gateway Start-up Guide, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.