Viessmann · Boiler troubleshooting

Boiler pump runs continuously after multi-boiler change

Vitodens 200-W B2HB

What is going on

When a Vitodens 200 B2HB goes from single to multi-boiler operation, coding address 30:0 can reset to 30:3, which keeps the boiler pump running continuously.

Likely causes

  • Coding address 30:0 automatically resets to 30:3 when switching from single boiler to multi-boiler operation

Check in this order

  1. Check that the coding address for each boiler is 30:0.
  2. Set it to 30:0 if necessary (see p. 59).

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 (multi-boiler)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service instructions, p. 83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.