Viessmann · Boiler troubleshooting

Field test of fixed high limit, simulation 2 (CSD-1)

Vitodens 222-FB2TB

What is going on

Checks the fixed high limit by running the boiler with minimal flow and then stopping flow completely. Only where required by law.

Check in this order

  1. Throttle the boiler valve until the burner runs with as little flow as possible.
  2. Run the boiler to high fire using the relays test.
  3. When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  4. Let the boiler temperature keep rising until the fixed high limit trips.
  5. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
  6. Reset the boiler control manually, since a tripped fixed high limit requires manual reset.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F, B2TB installation instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.