System type 1: single boiler with shunt pump to raise return temperature (modulating boiler)
What is going on
Single-boiler system with a shunt pump, used with a Vitorond 200, VD2 boiler. The boiler and DHW tank connect to the Vitotronic, and a heating circuit with mixing valve is fed from the boiler. Temperature sensor T2 controls the shunt pump; temperature sensor T1 controls flow reduction.
Check in this order
- Connect the boiler temperature sensor, outdoor sensor, and DHW tank sensor as shown in the system diagram.
- Connect temperature sensor T1 at plug aJA and temperature sensor T2 at plug aJB.
- Connect the shunt pump (sL) to the control unit as shown.
- When the boiler return temperature falls below the required minimum, sensor T2 switches on the shunt pump.
- If the minimum return temperature is still not reached, use sensor T1 to reduce the flow by at least 50%.
- Size the shunt pump so that bypassed water is about 30% of the total boiler flow rate.
- Set coding 4A and 4b as needed. Coding 4A:1 and 4b:1 are set automatically when T1 and T2 are connected.
Applies to: Vitotronic 300, Model GW2 with Vitorond 200, VD2 modulating boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 6-7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.