Viessmann · Boiler troubleshooting

Heating circuit behavior during DHW tank heating

Vitocrossal 300 CA3B

What is going on

Depends on the DHW priority setting (coding a2).

Check in this order

  1. Priority control (a2:2): supply set point goes to 32°F (0°C), mixing valve closes, heating circuit pump switches off.
  2. Without priority control heating circuit keeps the same set value.
  3. Modulating priority with mixing valve pump stays on and supply set point is reduced until boiler water set point is reached.

Applies to: Heating circuits with DHW priority

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.