Heating circuit behavior during DHW tank heating
What is going on
Depends on the DHW priority setting (coding a2).
Check in this order
- Priority control (a2:2): supply set point goes to 32°F (0°C), mixing valve closes, heating circuit pump switches off.
- Without priority control heating circuit keeps the same set value.
- Modulating priority with mixing valve pump stays on and supply set point is reduced until boiler water set point is reached.
Applies to: Heating circuits with DHW priority
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.