Viessmann · Boiler troubleshooting
Replace gas valve (LPG)
What is going on
Gas valve swap on a boiler set up for propane, including the LPG orifice and gaskets.
Check in this order
- Unplug the black valve connector and the white GDW2 and white gas pressure switch connectors.
- Remove the four M5 (4 mm hex) flange screws and set them aside.
- Disconnect the gas supply line and the compensation tubing.
- Remove the tube support and the four M5 (8 mm hex) manifold nuts.
- Remove the LPG orifice and both LPG gaskets. Replace the gaskets and clean the manifold surface.
- Install M5 studs in the new valve and tighten to the torque in the torque table.
- Reassemble in reverse order.
- Leak test the gas line and valve connections.
Applies to: Liquid propane (LPG)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.