System layout 4: radiator and underfloor circuits with DHW

Vitodens 200-W

What is going on

One direct radiator circuit and one underfloor circuit with a mixing valve, plus DHW storage. Radiator circuit flow must be at least 30% greater than underfloor flow, and total flow must be under boiler maximum.

Check in this order

  1. Confirm radiator circuit flow is at least 30% greater than underfloor circuit flow.
  2. Confirm total flow of both circuits is under boiler maximum.
  3. Install the mixing valve accessory kit and its temperature sensor on the underfloor circuit.
  4. Use a low-loss header if flow exceeds the limit on p. 30 or flow is unknown.
  5. Pipe the DHW circulating pump into the boiler.

Applies to: Mixed radiator and underfloor heating with DHW

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA installation manual, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.