Check the fixed high limit (STB)
What is going on
Test of the fixed high limit on the Vitotronic 100. The adjustable high limit is bypassed during the test.
Check in this order
- Hold down the test button (TÜV) for the test.
- Make sure a minimum flow is present. Minimum boiler flow should be 10% of the boiler flow at rated output.
- Reduce the heat consumption as far as possible. The adjustable high limit R is bypassed.
- Let the burner run until the boiler water reaches the safety temperature and the fixed high limit (STB) switches off.
- Release the test button (TÜV). The display shows fault D4.
- Wait until the boiler water is 15 to 20 °C (25 to 35 °F) below the set safety temperature.
- Press button E to reset the fixed high limit. Fault D4 clears.
Applies to: Vitotronic 100 GC1 fixed high limit test
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.