Weil-McLain · Boiler troubleshooting
Adjust high fire CO2 at the gas valve throttle screw
What is going on
Set the high fire CO2 to the target in the combustion table using the throttle screw.
Check in this order
- Run the boiler at high fire and let it stabilize.
- Read CO2 with the combustion analyzer.
- If CO2 is high, turn the throttle screw (2.5mm Allen) clockwise in small moves to lower the input.
- If CO2 is low, turn the throttle screw counterclockwise to raise the input.
- Let the boiler stabilize and read again after each move. Repeat until the target CO2 is reached.
- Confirm CO is within limits.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.