Example C shadow boiler field wiring (Shadows 2 to 4)
What is going on
Shadow 2 serves Zones 3 to 6 with Circulators 3 to 6. Shadow 3 serves Zones 7 to 10 with Circulators 7 to 10. Shadow 4 serves Zones 11 to 14 with Circulators 11 to 14. Each boiler has its own 120 VAC supply and boiler circulator. Each output is rated 2.0 A max.
Check in this order
- Wire each shadow boiler to 120 VAC power on L1.
- Wire each shadow boiler circulator to BOILER PUMP and its 2-pin plug at J4-4.
- Wire each zone circulator to its numbered output, rated 2.0 A max.
- Wire each zone thermostat to its W, R and C terminals.
- Wire the outdoor air and system sensors to J19 on each shadow boiler; sensors marked with an asterisk are for redundancy only.
Applies to: Example C shadow boilers 2, 3 and 4
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 29-30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.