Weil-McLain · Boiler troubleshooting

Example C shadow boiler field wiring (Shadows 2 to 4)

Evergreen Series 2

What is going on

Shadow 2 serves Zones 3 to 6 with Circulators 3 to 6. Shadow 3 serves Zones 7 to 10 with Circulators 7 to 10. Shadow 4 serves Zones 11 to 14 with Circulators 11 to 14. Each boiler has its own 120 VAC supply and boiler circulator. Each output is rated 2.0 A max.

Check in this order

  1. Wire each shadow boiler to 120 VAC power on L1.
  2. Wire each shadow boiler circulator to BOILER PUMP and its 2-pin plug at J4-4.
  3. Wire each zone circulator to its numbered output, rated 2.0 A max.
  4. Wire each zone thermostat to its W, R and C terminals.
  5. Wire the outdoor air and system sensors to J19 on each shadow boiler; sensors marked with an asterisk are for redundancy only.

Applies to: Example C shadow boilers 2, 3 and 4

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 29-30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.