Weil-McLain · Boiler troubleshooting

Example F multi-boiler piping and circulator notes

Evergreen Pro Series 2

What is going on

Setup notes for the Example F multi-boiler layout with variable primary circulator and isolation/bypass valves.

Check in this order

  1. Follow the control setting notes and use the Example F settings table as the starting point. Use the Wizard or the manual menus to enter them.
  2. Size the variable primary system circulator for the required flow. Pumps must deliver the flow each boiler needs.
  3. Follow the sizing guidelines in the manual and use sound engineering practice for the whole system.
  4. Provide an external relay and separate power for any boiler circulator whose load goes above 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush.
  5. Provide an external relay and separate power for any system circulator whose load goes above 2.0 A FLA.
  6. Follow the manual's piping instructions for both the boiler and the system.

Applies to: Evergreen Pro Series 2 multi-boiler installations (Example F)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.