Checking a damper output during a boiler call

Evergreen Pro Series 2

What is going on

Use this when a combustion air damper, flow switch or interlock output does not act the way the boiler should during a call for heat. The output's timing depends on whether it is set as a system or local damper.

Likely causes

  • Damper option set to SYSTEM DAMPER when LOCAL DAMPER is needed, or the reverse
  • Wrong priority or input assigned to the output
  • Burner not firing, so the output never energizes

Check in this order

  1. Confirm which damper option (SYSTEM or LOCAL) is assigned to the output being checked.
  2. With no call for heat, confirm the output is off.
  3. On a call, check that a SYSTEM DAMPER output energizes when the boiler starts pre-purge.
  4. Check that a LOCAL DAMPER output only energizes if this boiler is trying to fire.
  5. After the burner shuts off, confirm the output drops once post-purge is complete.

Applies to: Evergreen Pro Series 2 boilers, damper and interlock outputs

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Advanced Manual 550-100-581, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.