Weil-McLain · Boiler troubleshooting
Checking a damper output during a boiler call
What is going on
Use this when a combustion air damper, flow switch or interlock output does not act the way the boiler should during a call for heat. The output's timing depends on whether it is set as a system or local damper.
Likely causes
- Damper option set to SYSTEM DAMPER when LOCAL DAMPER is needed, or the reverse
- Wrong priority or input assigned to the output
- Burner not firing, so the output never energizes
Check in this order
- Confirm which damper option (SYSTEM or LOCAL) is assigned to the output being checked.
- With no call for heat, confirm the output is off.
- On a call, check that a SYSTEM DAMPER output energizes when the boiler starts pre-purge.
- Check that a LOCAL DAMPER output only energizes if this boiler is trying to fire.
- After the burner shuts off, confirm the output drops once post-purge is complete.
Applies to: Evergreen Pro Series 2 boilers, damper and interlock outputs
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Advanced Manual 550-100-581, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.