Cleaning the burner fan, Venturi tube and burner tube

Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

What is going on

Cleaning the fan and burner assembly and checking for gas leaks after reassembly.

Likely causes

  • Dirt on the fan impeller or housing.
  • Gasket between fan housing and burner plate damaged.

Check in this order

  1. Close the central gas shut-off valve before any burner work.
  2. Disconnect the Venturi mixing tube from the fan.
  3. Detach the Venturi mixing tube with the combination gas valve and gas connector pipe; detach connector pipes if needed.
  4. Detach the connector pipes from the fan and remove the fan.
  5. Clean the fan housing and impeller with compressed air.
  6. Vacuum the burner tube inside and out if necessary.
  7. Reassemble in reverse order and fit the gasket between fan housing and burner plate in the correct position. Replace it if damaged.
  8. Check for gas leakage at the screws and at the gasket between the fan housing and the burner plate.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner fan and Venturi

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.