Weil-McLain · Boiler troubleshooting

Test temperature limit

EGPEG

What is going on

Confirms the boiler shuts off burners when water reaches the limit setting and restarts when the setting is raised again.

Check in this order

  1. With the burners operating, lower the Boiler Temperature setting until the display reads below the actual boiler water temperature.
  2. Confirm the burners go off while the circulator keeps running.
  3. Raise the Boiler Temperature setting above the boiler water temperature.
  4. Confirm the ignition sequence resumes.

Applies to: EG and PEG Series 7 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.