Annual startup: clean the condensate trap
What is going on
Clean the condensate trap during the yearly startup if debris has collected in the reservoir or trap.
Likely causes
- Debris built up in the trap reservoir
Check in this order
- Turn off power to the boiler.
- Loosen the two stainless steel hose clamps on the flexible coupling.
- Slide the coupling off the 1 inch PVC pipe connected to the trap.
- Loosen the condensate trap inlet connection.
- Remove the trap and flush it clean.
- Refill the trap with fresh water before reinstalling, or reinstall it and fill it through the inspection caps near the flue connection.
- Check that the condensate line gasket is in place and tighten the inlet clamp nut by hand.
- Slide the flexible coupling back over the trap and drain piping and tighten the hose clamps.
- Check all connections for leaks.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.